How To Calculate Diesel Consumption For Generators

Categories

Recently Added Products

See Our Available Generators

Huge Range Of Generators Available

Choosing a diesel generator for a site, standby or off-grid application? Check the expected fuel use before comparing models. The right figure depends on the specific generator and the load it will supply, not just its kVA rating.

This guide shows you how to use a generator’s fuel data to estimate litres required, runtime and running costs. If you’re still comparing units, start with Bellwood’s diesel generator range.

There isn’t one fuel-use figure that applies to every diesel generator. To estimate your own fuel use, find the manufacturer’s fuel rate for your generator at the load you expect to run. Multiply that rate in litres per hour by the number of hours you need to operate.

Fuel required (litres) = fuel rate (L/h) × operating time (hours)

That gives you a starting point for planning fuel, runtime and cost. For a useful estimate, use data for the specific generator rather than a general figure for its kVA size.

Teksan 19Kva Single Phase Silenced Diesel Generator

What Information Do You Need?

Before you start, check the generator’s technical data and gather:

  • The make and model
  • Its rated output in kW and kVA
  • Whether the rating is for standby or prime operation
  • The expected electrical load, in kW or as a percentage of rated output
  • The manufacturer’s fuel rate at that load, in litres per hour
  • The number of hours it will run
  • Your delivered diesel price per litre
  • The tank’s usable capacity, if you’re estimating the time between refuelling

 

Pay attention to the conditions attached to the manufacturer’s figures. Fuel data may be listed at different load points and may specify a power factor or rating. Use a figure that matches the generator and duty you’re planning.

Calculate Fuel for a Fixed Load

If the generator will run at a fairly steady load, the calculation is simple.

Fuel required = manufacturer’s fuel rate × operating hours

For example, if the fuel rate for your model at the expected load is F L/h and you plan to run it for H hours, the estimate is:

F × H = estimated litres required

Here’s a worked example using hypothetical figures. These are for demonstration purposes only; they are not typical rates or data for a Bellwood generator.

Assume the manufacturer’s data for a particular generator gives a fuel rate of 18 L/h at the load you expect to run. You plan to operate it for 8 hours.

  • Fuel required: 18 L/h × 8 hours = 144 litres

 

Use your own generator manufacturer’s data and planned runtime to replace the example figures.

Genmac18Kva Single Phase Silenced Diesel Generator

Estimate Fuel Cost

Once you’ve estimated the litres required, multiply by the price you pay for diesel.

Fuel cost = litres required × diesel price per litre

Using the hypothetical example above, if the delivered diesel price were £1.20 per litre:

  • Estimated cost for 8 hours: 144 litres × £1.20 = £172.80
  • Estimated cost per hour: 18 L/h × £1.20 = £21.60

 

**The £1.20 figure is included for illustration, not as a current diesel price. 

Calculate Fuel Cost Per kWh

Cost per kWh can help when comparing the fuel cost of producing electrical energy at a particular load.

First, calculate the generator’s electrical output at that load. Then use the matching fuel rate:

Fuel use per kWh (L/kWh) = fuel rate (L/h) ÷ electrical output (kW)

Fuel cost per kWh = fuel use per kWh × diesel price per litre

For example, assume a 100 kW generator is running at 75% load, giving an output of 75 kW, and its hypothetical fuel rate at that load is 18 L/h:

  • Fuel use: 18 L/h ÷ 75 kW = 0.24 L/kWh
  • At the illustrative price of £1.20/L: 0.24 × £1.20 = £0.288 per kWh

 

This is an estimate for that model at that operating point. Use the generator’s rated kW output and the fuel rate for the same load. Don’t treat kVA as though it were kW. If you need to convert between them, use the power factor stated in the generator’s technical data.

Compare Fuel Use at Different Loads

Cost per kWh can help when comparing the fuel cost of producing electrical energy at a particular load.

First, calculate the generator’s electrical output at that load. Then use the matching fuel rate:

Fuel use per kWh (L/kWh) = fuel rate (L/h) ÷ electrical output (kW)

Fuel cost per kWh = fuel use per kWh × diesel price per litre

For example, assume a 100 kW generator is running at 75% load, giving an output of 75 kW, and its hypothetical fuel rate at that load is 18 L/h:

  • Fuel use: 18 L/h ÷ 75 kW = 0.24 L/kWh
  • At the illustrative price of £1.20/L: 0.24 × £1.20 = £0.288 per kWh

 

This is an estimate for that model at that operating point. Use the generator’s rated kW output and the fuel rate for the same load. Don’t treat kVA as though it were kW. If you need to convert between them, use the power factor stated in the generator’s technical data.

Compare Fuel Use at Different Loads

A generator’s fuel rate changes as the electrical load changes. The relationship isn’t necessarily linear, so doubling the load doesn’t always double fuel consumption.

If the manufacturer provides fuel rates at several load points, use them to compare the expected use for your operating pattern. This table shows how to make that comparison; fill it with the figures for the specific generator model.

Generator load

Manufacturer’s fuel rate

Estimated fuel for 8 hours

25%

Model data in L/h

Model data × 8

50%

Model data in L/h

Model data × 8

75%

Model data in L/h

Model data × 8

100%

Model data in L/h

Model data × 8

Don’t use these load percentages to assume a particular generator will consume a set number of litres. The fuel rate at each point must come from the manufacturer’s data for that model.

Calculate Fuel Use When the Load Changes

If the generator supplies different loads throughout the day, split the operating time into periods. Multiply each period’s fuel rate by the number of hours at that load, then add the results.

Operating period

Fuel rate for that load

Time at that load

Estimated fuel

Period 1

Model data in L/h

Hours

Rate × hours

Period 2

Model data in L/h

Hours

Rate × hours

Period 3

Model data in L/h

Hours

Rate × hours

Total

   

Add the period estimates

This is more useful than applying a single full-load or average figure to the whole day when the load varies significantly.

Estimate the Runtime From the Fuel Tank

To estimate how long the generator may run before refuelling, divide the usable fuel in the tank by the consumption rate at the expected load.

Estimated runtime (hours) = usable tank fuel (litres) ÷ fuel rate (L/h)

Use the tank’s usable capacity, not its total capacity. Leave the reserve required for your operation and follow the generator manufacturer’s instructions. If the load changes, use the fuel rates and hours for each period to estimate total consumption.

Pramac 60Kva Perkins Diesel Generator

What Affects Real-World Fuel Consumption?

The manufacturer’s fuel data is the best starting point, but actual use can differ. The generator’s load, model, condition and operating environment all matter. Maintenance and site conditions can also affect performance.

Very light loading over long periods can be unsuitable for some diesel engines. The minimum load and recommended operating conditions are model-specific, so check the manual or ask the manufacturer rather than applying a universal “ideal” load percentage.

For critical operations, record actual fuel use and compare it with the estimate. That helps with budgeting and fuel deliveries, and can highlight when the generator is operating differently from the plan.

Choosing a Diesel Generator

If you’re factoring in fuel costs when comparing generator options, browse Bellwood’s diesel generators or contact the team. Have your required output, expected load and operating hours ready so you can discuss a suitable generator and its manufacturer’s fuel data.

Choosing a Diesel Generator

Choosing a diesel generator involves more than comparing kVA ratings. Bellwood can help you assess a suitable generator for your equipment, expected running hours and site requirements. View our diesel generator range or contact Bellwood to discuss your application.